| Housing: self extinguishing ABS |
| Case: CX: frontal 32x74mm; depth 60mm, L: frontal 38x185mm; depth 76mm |
| Mounting: CX: panel mounting in a 29x71mm cut-out, L: panel mounting in a 31x150mm cut-out |
| Front protection: IP65 with gasket |
| Connections: disconnectable connectors (12-14 pin or 14-6 pin or 16-9 pin) |
| Power supply: 12Vac/dc -10% ÷ +15%, 24Vac/dc ±10% 50/60Hz, 110/230Vac ±10% 50/60Hz |
| Power absorption: 5VA max |
| Probe inputs: up to 4 NTC or 3 NTC + 1 (4÷20mA)/0,5V |
| Configurable digital inputs: 4 |
| Relay outputs: SPDT 8(3)A, 250Vac, SPDT 5(2)A, 250Vac |
| External relay output: 0÷12Vdc- 40mA max |
Analog output: PWM signal (single-fan module), 4÷20mA (fan module), 0÷10V (fan module)
|
| Data storing: on the non-volatile memory (EEPROM) |
| Operating temperature: -10÷60°C (14÷140°F) |
| Storage temperature: -30÷85°C (-22÷185°F) |
| Relative humidity: 20÷85% (non condensing) |
| Measuring and regulation range: pressure probe: 0÷50bar, NTC probe -40÷110°C (-40÷230°F) |
| Resolution: 0,1°C or 1°F (selectable) |
| Accuracy (ambient temperature): ± 0,7°C ± 1digit |